Accuchiller KSE Series Packaged Outdoor Chiller

Description

Image title

KSE Series industrial outdoor air-cooled chillers feature a compact, all-in-one package designed to minimize installation cost, maximize usable space and lower electric bills. Designed for harsh outdoor environments KSE Series chillers require no options to operate within the standard -20°F to 125°F ambient environment conditions. Standard process fluid temperatures of 20°F to 80°F are ideal for industrial applications. The modular design allows up to 12 refrigeration circuits to be combined into a single system for up to 720 tons of cooling capacity.

Chillers are available with or without integrated pumping packages, including high and low pressure pumping with dedicated stand-by and built-in pressurized and non-pressured tanks.

KSE Series chillers come standard with Dynamic Lift technology to continuously calculate the lowest allowable refrigerant pressure for any combination of operating conditions for maximize chiller energy savings and stable process fluid temperatures of +/- 1°F.

Features

  • Wide operating conditions
    • Ambient Environment: -20°F to 125°F
    • Process Fluid Circuit: 20°F to 80°F
  • Integral air-cooled rugged microchannel condenser for class-leading efficiency
  • Innovative PLC Control System with a large high-resolution color touch-screen operator interface and an extensive list of operational information including remote monitoring
  • Direct drive scroll compressors for low maintenance and energy efficiency
  • Compressor staging for capacity control with optional hot gas bypass for even greater unloading capabilities
  • Compressor anti-cycle and start-up timer
  • Lead/lag compressor staging to alternate primary compressor
  • Brazed plate evaporators maximize performance and increase resistance to costly freeze-up failures
  • Standard variable-speed drive fans reduce energy usage and provide optimum part-load performance for industry-leading IPLV, all while reducing noise levels for sound-sensitive environments  
  • C-UL 508A listed and labeled control panel
  • In-line evaporator strainers assure full evaporator performance
  • Single point connection for electric hookup at control cabinet
  • Electronic expansion valves
  • Liquid line solenoid valves to extend compressor life
  • Refrigerant sight glasses
  • Liquid line filter driers with removable cores
  • High and low refrigerant pressure switches
  • Alarm horn with silence button
  • 3-phase power monitoring and safety protection
  • Environmentally balanced 410a refrigerant

Available Options

  • High and low pressure pumping with dedicated stand-by pump for quick and easy installation
  • Rotary non-fused disconnect switch
  • Hot-gas bypass minimum load capacity control
  • 5-year compressor parts warranty
  • Expert field start-up provided by qualified service personnel
  • CONNEX 4.0 for system-wide control

Image title